Calculate the BTUs Per Hour that Your Intel® Server System Generates


Last Reviewed: 24-Oct-2016
Article ID: 000006784

How can I calculate the British thermal units (BTU) per hour my server generates?

  1. Get the wattage of your power supply. For example, the Intel® Server System R1208WT2GSR has one 750W power supply.
  2. Divide the wattage by the efficiency, found in the Technical Product Specification (TPS). Our example server shows 91% efficiency when running at 100% load; 750/0.91 = 824 Watts consumed
  3. Multiply the Watts consumed by 3.41214 to get BTU/h. Our example is: 824*3.41214~=2,812 BTU/h